How To Size A Cable -
Cable sizing is not merely about matching a conductor to a load current. It is a multi-variable optimization problem that ensures safety, reliability, efficiency, and longevity of an electrical installation. An undersized cable causes overheating, voltage drops, energy losses, and fire hazards. An oversized cable wastes material, increases installation costs, and may create termination difficulties.
Example : 230 V single-phase, L=80 m, I=20 A, cosφ=0.85, 4 mm² Cu (R=4.6 Ω/km, X=0.09). Vd = [2×80×20×(0.0046×0.85 + 0.00009×0.526)] / 1000 = 12.8 V → 5.6% > 3%. Fail. Increase to 6 mm². During a short circuit, heat is generated faster than it can dissipate (adiabatic process). The cable must survive until protection clears the fault. how to size a cable
: 3% for power, 5% total including distribution. Cable sizing is not merely about matching a
is given by tables (IEC 60287, NEC Table 310.16). For example: For example: | Copper
| Copper, XLPE, 90°C, 30°C ambient, free air | 1.5 mm² → 24 A | 2.5 mm² → 32 A | 4 mm² → 42 A | | Aluminum, PVC, 70°C, buried | 16 mm² → 70 A | etc. |
$V_d = \frac\sqrt3 \times L \times I \times (R \cos\phi + X \sin\phi)1000$

